Cisco Nexus 7706 Hardware Installation Manual page 25

Nexus 7000 series
Hide thumbs Also See for Nexus 7706:
Table of Contents

Advertisement

Preparing the Site
5
6
7
8
Note
Figure 4: Clearances Required Around the Chassis, on page 12
conventional cold-aisle to hot-aisle systems which include rack enclosures with perforated front and rear
doors. The information given above does not apply to enclosures which have a solid rear or front door or wall
with other inlet or exhaust configurations. We recommend consulting a cooling professional if a solid rear or
front door is used.
OL-31330-01
Nearest object or inside of cabinet (no
side clearance required)
Air intake from the cold aisle for all
modules and power supplies
Air exhaust to the hot aisle for all
modules and power supplies
No left side clearance required (no
airflow on left side)
13
Chassis depth
Note
The chassis depth will increase by 2
inches when the 76mm Gen 2 fan tray
(N77-C7706-FAN-2) is used.
14
Clearance required between the front of the chassis
and the inside of the cabinet (if used) or the edge of
the cold aisle (if no cabinet) for the cable
management frames and the optional front doors
15
Front service clearance required for installing the
chassis and replacing the modules on the front of the
chassis
shows the clearance requirements for
Cisco Nexus 7706 Hardware Installation Guide
Clearance Requirements
13