Installing The Chassis On A Four-Post Rack Or Cabinet - Cisco Nexus 7706 Hardware Installation Manual

Nexus 7000 series
Hide thumbs Also See for Nexus 7706:
Table of Contents

Advertisement

Installing the Chassis on a Four-Post Rack or Cabinet

Note
c) Screw in the four captive screws to the chassis and tighten each screw to 8 in-lb (0.9 N·m).
Step 11
If you removed any power supplies before moving the chassis, reinstall each one as follows:
a) Determine which power supply slots to fill and ensure that each of those slots is open.
If you are using the combined or power supply redundancy mode, you can use any slot for the power supply that
you are installing. If you are using the input-source or full redundancy mode, you must group the power supplies
that are to be connected to the same grid on either the left or right power supply slots in the chassis (that is, place
the power supplies for grid A in slots 1 or 2 or both slots and place the power supplies for grid B in slots 3 or 4 or
both slots).
b) Place one hand on the front of the power supply and place your other hand under it to support its weight.
c) Align the power supply to an open power supply slot.
Note
d) Slide the power supply all the way into the slot until its release handle clicks and the module stops.

Installing the Chassis on a Four-Post Rack or Cabinet

Before you begin
• Verify that the chassis shipment is complete and undamaged.
• Verify that a rack or cabinet is installed and secured to the subfloor.
• Verify that the bottom-support rails have been attached to the lowest possible RU in the rack or cabinet
• If there are other devices in the rack, verify that the devices that are heavier than this chassis are installed
• Verify that the data center ground is accessible where you are installing the chassis.
• Verify that you have the following tools and equipment:
Cisco Nexus 7706 Hardware Installation Guide
26
The two alignment pins on the fan tray (on the top and one on the bottom) should go into holes in the
chassis and the four captive screws on the fan tray should align to screw holes in the chassis.
The alignment bracket on top of the power supply should align to a track at the top of the slot and a bar
at the bottom of the power supply should be guided by a track at the bottom of the slot.
Warning
Stability hazard. The rack stabilizing mechanism must be in place, or the rack
must be bolted to the floor before you slide the unit out for servicing. Failure to
stabilize the rack can cause the rack to tip over.
Statement 1048
and there is 9 RU (15.75 inches [40.0 cm]) of space above the rails to install the chassis.
below where you are going to install the chassis and lighter devices are installed above where you are
going to install the chassis.
• Mechanical lift capable of lifting the full weight of the chassis and its installed modules
Installing the Switch Chassis
OL-31330-01

Advertisement

Table of Contents
loading

Table of Contents