Megohmmeter Model 1000N/1100N
When the guard terminal is connected at "B", the instrument measures
the current "I" and not the surface leakage current "i
included in the measurement. See Figure 5. This type of measurement
will give the true value of
the
resistance
providing the "Ry" and
"Rz" are not too low.
9ROWDJH0HDVXUHPHQWV6DIHW\&KH.N
Insulation resistance tests are to be carried out on non-energized circuits
only. Voltage measurements are made as a safety precaution. If any
voltage is present do not proceed with insulation resistance testing. This
instrument can measure both AC or DC voltages. For voltage
measurements, proceed as follows:
• The PUSH-TO-TEST button should be in the OFF position.
• Connect the instrument with the voltage leads connected between the
Line (-) and Earth (+) terminals on the unit.
• Read the voltage directly on the voltage scale.
"Rx",
To EARTH
Terminal
Figure 6
- 14 -
Ry
Rx
A
i
Figure 5
- LINE
+ EARTH
MEGOHMMETER
1
", which is not
To Guard
Terminal
B
i 1
Rz
To LINE
Terminal
C