Megohmmeter Model 1000N/1100N
,QVXODWLRQ0HDVXUHPHQW&RQQH.WLRQV
Conductor under test
GUARD
- LINE
MEGOHMMETER
Figures 8 and 9 show the connection for testing insulation from a supply
conductor to a ground (motor frame). The connection to the guard
terminal is used to eliminate the effects of surface leakage across
exposed insulation at one end of the cable. Refer to the section "Utilizing
the Guard Terminal." The cable should be disconnected at both ends to
avoid leakage through switchboards and panels.
Conductor under test
GUARD
- LINE
MEGOHMMETER
+ EARTH
Figure 7
+ EARTH
Figure 7 shows the con-
nections to measure the
insulation of one conductor
to the other conductors.
The
disconnected at both ends
to avoid leakage through
switchboards and panels.
Figure 8
- 16 -
cable
should
be