Megohmmeter Model 1000N/1100N
Groundable Points
0HDVXUHPHQW5HVXOWV
Specific measurement results for each individual application of the Model
1100N are difficult to determine. The definitive information on which
voltage level to apply, as well as which measurement values will indicate
a proper resistivity, should be determined by the manufacturer of the
conductive flooring or tiles.
The following values (based on EOS/ESD, S4.1-1990) may serve as a
minimum resistivity level which has been proven to provide an
appropriate level of protection in the manufacturing environment.
Resistance from test electrode to a groundable point (Figure 17):
Measured value: ≤ 10,000 megohms (10 gigohms)
Resistance from electrode to electrode (Figure 16):
Measured value: ≥ 1 megohm
Table Top
GUARD
- LINE
MEGOHMMETER
Figure 17
- 34 -
Electrode
+ EARTH