Mitsubishi PKH-1.6GKLH Technical & Service Manual page 48

Pkh series. wall mounted
Table of Contents

Advertisement

6. WRONG WIRING ON SITE
6-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller
when the POWER button is pressed. The beep sound will also not be heard.
6-2 Phenomenon due to wrong wiring between indoor and outdoor units
Wrong wiring
Indoor
1
2
3
Indoor
1
2
3
Indoor
1
2
3
Indoor
1
2
3
Indoor
1
2
3
Disconnection between 1 and 1 or 2
and 2.
Disconnection between  and .
OC229A
Mode
Thermostat
OFF
Outdoor
COOL
1
ON
2
3
OFF
HEAT
ON
OFF
Outdoor
1
COOL
ON
2
3
OFF
HEAT
ON
OFF
Outdoor
1
COOL
ON
2
3
OFF
HEAT
ON
Outdoor
OFF
1
COOL
2
ON
3
OFF
HEAT
ON
OFF
Outdoor
COOL
1
ON
2
3
OFF
HEAT
ON
OFF
COOL
ON
OFF
HEAT
ON
COOL
OFF
HEAT
ON
Phenomenon
Operation stops.
-Way valve turns ON. 9 minutes later, check code "P8" appears
on remote controller display.
Cooling operation. Several minutes later, check code "P8" appears
on remote controller display.
Normal operation.
Outdoor unit stops.
Operation stops. 9 minutes later, check code "P8" appears on
remote controller display.
Operation stops.
Operation stops. 27 minutes later, check code "P8" appears on
remote controller display.
Outdoor unit stops.
Operation stops. 9 minutes later, check code "P8" appears on
remote controller display.
Operation stops.
Operation stops. 27 minutes later, check code "P8" appears on
remote controller display.
Outdoor unit stops.
Operation stops. 9 minutes later, check code "P8" appears on
remote controller display.
Operation stops.
Operation stops, 27 minutes later, check code "P8" appears on
remote controller display.
Outdoor unit stops.
Operation stops. 9 minutes later, check code "P8" appears on
remote controller display.
Operation stops.
Operation stops. 27 minutes later, check code "P8" appears on
remote controller display.
Operation stops.
Operation stops. 9 minutes later, check code "P8" appears on
remote controller display.
Operation stops. -way valve turns OFF.
27 minutes later, check code "P8" appears on remote controller
display.
Normal operation.
Operation stops. -way valve turns ON.
Operation stops. 27 minutes later, check code "P8" appears on
remote controller display.
8