Mitsubishi PKH-1.6GKLH Technical & Service Manual page 46

Pkh series. wall mounted
Table of Contents

Advertisement

3-1 Outdoor coil temperature
To obtain data on the outdoor coil temperature, add the number of bits of lighting LEDs, and see the graph below to find
the temperature.
3-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan rota-
tional frequency.
1PUH-1.6/2KA
<50HZ>
Type
800
600
400
200
0
50
Fan output step (bit)
3-3 Total time of compressor operation
Compressor operation time is indicated in 26 hour units. To obtain the compressor operation time, add the hours of light-
ing LEDs. During the compressor operation time indication, SW2 is not available.
3-4 Check code indication
● When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes
time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW-1 and
SW-2 are OFF, the check code is indicated.
● If the outdoor controller board receives the compressor ON command from the indoor controller board during check
mode the indication changes to output state indication.
● By pressing SW2 during normal operation, operation will continue.
● The latest check code is indicated.
OC229A