2-5 Auto vane control
ADDRESS
UNIT No.
FUNCTION No.
°C
SELECTION No.
AM
PM
FUNCTION
AM
TEST RUN
PM
CHECK
TEMP.
ON/OFF
10°
30°
60°/ 50°
70°/ 60°
Swing
Changes by pressing
the VANE button.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the airflow direction in automatically set to 10°. After, it can be changed to
another direction with VANE button on the remote controller.
<Auto return>
When 0° or 60° airflow is set with fan speed on LOW, "1Hr" appears below the room temperature display. One hour later
the direction changes to 10° degrees, automatically and "1Hr" disappears.
(2) HEAT operation
At the start-up of HEAT operation, discharge direction depends on the setting of the last operation.
After, it can be changed to another direction with VANE button. The discharge direction shifts to 10° regardless of the
remote controller settings under any of the following conditions.
● Thermostat OFF
● Defrosting
● Indoor fan speed EXTRA-LOW in hot adjustment
OC229A
<How to operate>
To change the airflow direction, press VANE button.
NOTE: Airflow direction can be set by the indoor dip switch SW-1.
HEAT•FAN/ COOL•DRY
OPERATION
1
1
Available in COOL operation with fan speed on HIGH or
in HEAT operation.
Unavailable in DRY operation.
If fan speed changes from HIGH to LOW during 0°
downward airflow in COOL mode, the direction auto-
matically changes to 10°.