54
Requirements for the installation site
The drive must be installed in a cabinet. Check the installation site according to the
requirements below. Refer to
data
Cooling air flow
Provide the drive with the amount of fresh cooling air given in Technical data /
ratings
IT (ungrounded) systems
A drive equipped with no EMC filter or with EMC filter +E210 is suitable for IT
(ungrounded systems). If the drive is equipped with EMC filter +E202, disconnect
the filter before connecting the drive to an ungrounded system. For detailed
instructions on how to do this, please contact your local ABB representative.
WARNING! If a drive with EMC filter +E202 is installed on an IT system [an
ungrounded power system or a high resistance-grounded (over 30 ohms) power
system], the system will be connected to earth potential through the EMC filter
capacitors of the drive. This may cause danger or damage the unit.
Required tools
• 3 mm (0.12 in.) screw driver
• torque wrench with 500 mm (20 in.) or 2 x 250 mm (2 x 10 in.) extension bar
• 19 mm (3/4 in.) socket
for frame size R7: 13 mm (1/2 in.) magnetic end socket
for frame size R8: 17 mm (11/16 in.) magnetic end socket.
Installation
+E210
Type designation label
+E210
Serial number label
for the allowed operation conditions of the drive.
or
US
tables.
Dimensional drawings
for frame details. See
Technical
IEC