Download Print this page

Juniper PTX10002-60C Quick Start Manual page 3

Packet transport router

Advertisement

Unpack the PTX10002-60C
The PTX10002-60C chassis is a rigid sheet metal structure that houses the hardware components. The PTX10002-60C is shipped
in a cardboard carton, secured with foam packing material. The carton also contains an accessory kit with a Documentation
Roadmap card. The Documentation Roadmap includes the warranty and WEEE compliance statement, as well as a QR code
and useful links that help you find more detailed information about the PTX10002-60C.
CAUTION:
PTX10002-60C routers are maximally protected inside the shipping carton. Do not unpack the
PTX10002-60C until you are ready to begin installation.
Move the shipping carton to a staging area as close to the installation site as possible, but where you have enough room to
1.
remove the system components.
Position the carton so that the arrows point upward.
2.
Open the top flaps on the shipping carton.
3.
Remove the accessory kit and verify the package contents: One pair of front-mounting rails, One pair of rear-mounting blades,
4.
24 flat-head M4x6-mm Phillips mounting screws, RJ-45 cable and RJ-45 to DB-9 serial port adapter, AC or DC power cords
with plugs that are appropriate for your geographical location, Documentation Roadmap card, End User License Agreement.
Pull out the packing material holding the PTX10002-60C in place.
5.
Remove the chassis from the box.
6.
Save the shipping carton and packing materials in case you need to move or ship the chassis later.
7.
Mount the PTX10002-60C in a Rack
Mount the PTX10002-60C in a 19-in four-post rack using the included mounting brackets. The shipping carton contains two
front-mounting rails with two matching rear-mounting blades. This configuration allows either end of the PTX10002-60C to be
mounted flush with the rack and still be adjustable for racks with different depths. The minimum distance the front and rear rack
rails can be spaced apart is 28 in. (71.1 cm) front to back. The maximum distance the front and rear rack rails can be spaced apart
is 36 in. (91.4 cm) front to back.
NOTE:
If you are mounting multiple units in the rack, mount the heaviest unit at the bottom and mount the others
from bottom to top in order of decreasing weight. The PTX10002-60C weighs 80.5 lbs (36.5 kgs). Installing the
switch in a rack requires either a mechanical lift or two people to lift the device and another person to secure it to
the rack.
Attach the ESD grounding strap to your bare wrist and to a site ESD point.
1.
Place the rack in its permanent location, allowing adequate clearance for airflow and maintenance, and secure it to the building
2.
structure.
Decide whether the field-replaceable unit (FRU) end or the port end of the PTX10002-60C must be placed at the front of the
3.
rack. Position the PTX10002-60C in such a manner that the
Using a Phillips screwdriver, remove the six screws on each side of the chassis that hold the cover to the chassis (see
4.
These screws will be replaced with the mounting screws included in the box.
Copyright © 2018, Juniper Networks, Inc.
labels on components are next to the hot aisle.
AIR OUT
PTX10002-60C Quick Start Guide
Figure
2).
3

Advertisement

loading