11.4.5 The I/O-FORCE LIST
Independently of the currently running PLC program and the status of the hardware, the PLC inputs
and outputs can be set or reset via the I/O-FORCE LIST.
Activation
You are on the PLC main page.
Selecting inputs
and outputs for
the I/O FORCE LIST
February 2012
DANGER
The I/O-FORCE LIST can overrule safety-relevant monitoring operations in the PLC
program!
This could lead to damage to property or persons.
Ensure that hanging axes are supported.
Consult the machine manufacturer!
Switch to the next soft-key row.
Soft key for calling the I/O-FORCE LIST function.
Press the INSERT LINE soft key.
Select the inputs and outputs by entering their symbolic or absolute addresses.
Note
The TABLE, the WATCH LIST or the TRACE IN-CODE function can be called before and inputs and
outputs added to the I/O-FORCE LIST via the soft key ADD TO I/O-FORCE LIST.
Enter the value 0 or 1 which is to be "forced".
If required, add a comment.
Note
If the cursor is in the SYMBOL or ADDR column, you can sort the list alphanumerically by pressing the
ORDER soft key.