Installation
Vent Configurations with Horizontal Termination
Horizontal sections require a ¼" (6mm) rise every 12" (305mm) of travel.
A maximum of four (4) 45° or 90° elbows may be used. Of these elbows, only one (1) may be a
horizontal elbow (see illustration).
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
positions. NOTE: Restrictor positions are based upon lab tests. The ideal restrictor position may
vary slightly, especially when the termination is near a demarcation line.
Diffuser set to closed position (stock).
21' max (6.3m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
© Travis Industries
(for qualified installers only)
Exhaust Restrictor Position #5
Exhaust Restrictor Position #4
Exhaust Restrictor Position #1
Min. 2' (0.61m) Rise Required
Horizontal Elbow
Horizontal elbows are elbows placed between
two horizontal sections of pipe. One 45° or 90°
horizontal elbow is allowed for this configuration.