3:1 power system. 380/400/415v 50/60hz 4 to 20 kva
Hide thumbs Also See for Nfinity:
Table of Contents

Advertisement

General & Environmental
Unit Rating
Conducted and Radiated EMC Compliance
Compliant Safety Standards
Compliant Immunity Standards
Mechanical
Width
Dimensions:
Depth
Height
Environmental
Operating Temperature (max)
Relative Humidity
Maximum operating altitude
Nominal heat dissipation
Acoustic noise level
Input Data
Nominal input voltage
Power factor
Input frequency (nominal)
Input frequency range
Battery Module
Number of lead acid batteries
Number of battery cells
Battery capacity
Autonomy time (full load)
Maximum charge current (full load)
Nominal Voltage
Recharge Time
Output Data
Output voltage
Voltage regulation
Voltage stability (100% step load)
Recovery time
Voltage distortion:
Output frequency
Efficiency at 100% load
Efficiency at 100% load (transformer models)
Output overload capability

SPECIFICATIONS

Units
kVA
kW
EN50091-1-1, EN60950, CE, Low Voltage Directive
Units
mm (in)
Units
C (F)
%
M (Ft)
W
(BTUH/hr)
dBA
Units
VAC
Cos Ø
Hz
Hz
Units
A/hr
minutes
A
VDC
Hrs
Units
VAC
%
%
msec
%
Hz
%
%
%
46
Configuration
4
8
12
2.8
5.6
8.4
EN 50091-2 Class A
EN61000-4-2,3,4,5,6
12 Bay
508 (20)
711 (28)
1346 (53)
0° - 40° (32° - 104°)
0-95% non-condensing
3,000 (10,000)
311
622
933
(1062)
(2124)
(3186)
<62 @ 1 metre (39 in)
380/400/415 (380 V has output transformer)
>.80
50
40-70
10
60
9
6 (with an equal number of Battery & Power
Modules in a non-redundant configuration)
3
120
<6 (to 90% capacity)
220/230/240 (220V requires output transformer)
±3
±7
96
<3 THD, linear load
<7 THD, non-linear load
50
91
89
>100% - 110% operates indefinitely
111% - 150% operates for 8 sec
151% - 200% operates for 0.25 sec
>201% operates for 2 cycles
16
20
11.2
14.0
1244
1265
(4248)
(4320)

Hide quick links: