Communications; Com Ports; Com 1 - Relay Contacts; Com 2 - Serial - Liebert Nfinity User Manual

3:1 power system. 380/400/415v 50/60hz 4 to 20 kva
Hide thumbs Also See for Nfinity:
Table of Contents

Advertisement

COM Ports

Nfinity is able to communicate through multiple
communication ports simultaneously. Only use
Liebert provided communication cards. Only
connect SELV circuits when connecting to any
communication port.
5
4
9
8
Pin Assignment

COM 1 - Relay Contacts

Relay contacts are available through a DB-9F
communications connector. Contact closure
provides the following:
Pin
Assignment
1
Low Battery (normally open)
4
UPS shutdown in battery mode
(5-12 VDC for 1.5 sec)
5
Common
7
Low Battery (common)
8
On Battery (common)
9
On Battery (normally open)
The contacts are rated 48VDC, 1 amp maximum
and are compatible with the MultiLink software.

COM 2 - Serial

Nfinity is able to communicate via Liebert
proprietary protocol. The pin-out configuration of
the DB-9 connector is:
Pin
Assignment
2
Transmit Data
3
Receive Data
5
Common

COMMUNICATIONS

3
2
1
7
6
Intellislot
The following communication cards may be used
with Nfinity:
• Intellislot
SNMP cards - allows the Nfinity
communicate intelligently with your Ethernet
network. The SNMP card must be installed in
port 1; any additional cards can be added in
consecutive ports.
• Intellislot
MultiPort4 cards - allows up to
four client computer systems to
simultaneously monitor the status of Nfinity.
• Intellislot
Relay Contacts cards - provides
contact closures for remote monitoring of
alarm conditions; On Battery, On Bypass, Low
Battery, Summary Alarm, UPS Fault and On
UPS signals. It will integrate with AS400
computers (additional cable required) and
other monitoring systems.
18
Ports

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Nfinity and is the answer not in the manual?

Table of Contents