COM Ports
Nfinity is able to communicate through multiple
communication ports simultaneously. Only use
Liebert provided communication cards. Only
connect SELV circuits when connecting to any
communication port.
5
4
9
8
Pin Assignment
COM 1 - Relay Contacts
Relay contacts are available through a DB-9F
communications connector. Contact closure
provides the following:
Pin
Assignment
1
Low Battery (normally open)
4
UPS shutdown in battery mode
(5-12 VDC for 1.5 sec)
5
Common
7
Low Battery (common)
8
On Battery (common)
9
On Battery (normally open)
The contacts are rated 48VDC, 1 amp maximum
and are compatible with the MultiLink software.
COM 2 - Serial
Nfinity is able to communicate via Liebert
proprietary protocol. The pin-out configuration of
the DB-9 connector is:
Pin
Assignment
2
Transmit Data
3
Receive Data
5
Common
COMMUNICATIONS
3
2
1
7
6
™
Intellislot
The following communication cards may be used
with Nfinity:
™
• Intellislot
SNMP cards - allows the Nfinity
communicate intelligently with your Ethernet
network. The SNMP card must be installed in
port 1; any additional cards can be added in
consecutive ports.
™
• Intellislot
MultiPort4 cards - allows up to
four client computer systems to
simultaneously monitor the status of Nfinity.
™
• Intellislot
Relay Contacts cards - provides
contact closures for remote monitoring of
alarm conditions; On Battery, On Bypass, Low
Battery, Summary Alarm, UPS Fault and On
UPS signals. It will integrate with AS400
computers (additional cable required) and
other monitoring systems.