Chapter 7: Specifications - Liebert Vertiv GXT5 Installer/User Manual

Table of Contents

Advertisement

Chapter 7: Specifications

Table 7-1 UPS Specifications, 750 VA and 1000 VA models
MODEL GXT5-
RATING
Dimensions, D×W×H, in. (mm)
Unit
Shipping
Weight, kg (lb)
Unit
Shipping
Input AC
Voltage Range (typical)
90% ~ 100% loading
70% ~ 90% loading
50%~70% loading
0%~50%
Frequency
Input Power Cord
Output AC
Output Receptacles
Voltage
Waveform
Utility (AC) Model
Overload
Internal Battery Charger
Charger Current, A
Battery Parameters
Type
Qty×V×Rating
Battery Mfr./Part#
Back-up time
Recharge Time
Bypass Parameters
Upper-limit selections
Lower-limit selections
Disable-bypass operation
Vertiv | Liebert® GXT5™ | Installer/User Guide
750IRT2UXL*
750 VA/750 W
23.5 (51.7)
230 VAC nominal; variable based on output load
200/208/220/230/240 VAC (user-configurable); ±3%
>200% for 250 ms; 150 to 200% for 2 seconds
125 to 150% for 50 seconds; 105 to 125% 60 seconds
Valve-regulated, non-spillable, lead acid
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal
When the input frequency prevents synchronous operation.
750IRT2UXLE
1000IRT2UXL*
15.7 x 16.9 x 3.4 (400 x 430 x 85)
24.3 x 22.4 x 10.3 (617 x 570 x 262)
16.5 (36.3)
21 (46.2)
23.5 (51.7)
168 to 288 VAC
150 to 288 VAC
115 to 288 VAC
115 to 288 VAC
40 Hz to 70 Hz; Auto Sensing
C14
C13 × 8
Sine wave
default 2.2 A; Maximum 8 A
3 × 12V × 9.0 Ah
LEOCH DJW12-9.0
See
Battery Run Times
on
Batteries Only)
+10%, +15%, +20%; default +10%.
-10%, -15%, -20%; default -15%
1000IRT2UXLE
1000 VA/1000 W
21 (46.2)
page
118.
105

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents