Liebert Nfinity User Manual page 35

3:1 power system. 380/400/415v 50/60hz 4 to 20 kva
Hide thumbs Also See for Nfinity:
Table of Contents

Advertisement

Change Settings Menu, cont'd
Max Load Alarm Set: Allows an alarm to set
when Nfinity's load reaches a specific level.
Max Load Alarm
Mode
Set Threshold
Alarm Mode
Max Load Alarm Mode
Enable
* Disable
Set Threshold
Max Load Alarm Set
Threshold kVA = xx.x
UPS Shutdown Delay: Delays UPS shutdown for
specified amount of time after receiving shutdown
command via communications (serial or SNMP).
UPS Shutdown Delay
xxx Seconds
Redundant Alarm Set: Sets Alarm to notify user
when redundancy is no longer available.
Redund Power
Alarm Set
N+1 redundant
* Disable
Service Contact: Set a contact for the user to
reach if problems occur.
Service Contact
Company
Contact Number
Company Name
LIEBERT CORPORATION
Contact Number
WWW.LIEBERT.COM
Remote Shutdown: Enables / Disables the
Remote Communications Shutdown.
If you are using MultiLink™ software, this
parameter should be enabled in order for the UPS
output to be turned off once the operating system
has been shut down.
Remote comms Shutdn
* Enable
Disable
External Battery: Sets total amp-hour for external
batteries to provide a more accurate run time
remaining value on the LCD and through
communications.
External Battery
Amp-hour
> Charge Current
External Batt Config
Enter total amp-hour
0000
External Batt Config
Enter charge current
00.0
Enter the following when using the External
Battery Cabinets with Chargers.
(P/N: PB10SLF105WC-CE)
# of Cabinets
1
2
3
4
5
6
Bypass Alarm Mode: Allows the user to enable/
disable alarm, indicating that the bypass is not
qualified.
Bypass Alarm Mode
* Enable
Disable
Intelli-Battery Cab: Allows the user to enter the
quantity of intelligent battery cabinets installed.
Enter Intelli-
Battery cabinet
count
x
29
Charge
AH Value
Current
0091
7.0
0182
14.0
0273
21.0
0364
28.0
0455
35.0
0546
42.0