Liebert Nfinity User Manual page 34

3:1 power system. 380/400/415v 50/60hz 4 to 20 kva
Hide thumbs Also See for Nfinity:
Table of Contents

Advertisement

Change Settings Menu, cont'd
Auto Battery Test: Configure when and how often
the Nfinity's automatic battery test will run. This
test is designed to ensure Battery system integrity
and provide early warning of problems.
Auto Battery Test
Interval
Start Day
Start Time
Interval
Battery Test Intrvl
1 week
* 2 weeks
3 weeks
4 weeks
6 weeks
Disabled
Start Day
Battery Test Weekday
WED
Start Time
Battery Test Time
06:00
Low Battery Warning: Notifies user how much
runtime is available; can be set from 1 to 30 minutes.
Low Battery Warning
02 Minutes
Auto Restart: Automatically restarts once both
delay parameters (battery capacity percentage
and countdown timer) are met.
Auto Restart
Mode
Auto Restart Batt %
Auto Restart Delay
Auto Restart Mode
Auto Restart Mode
* Enable
Disable
Auto Restart Batt %
Auto Restart Batt %
0%
10%
* 25%
40%
60%
80%
Auto Restart Delay
Auto Restart Delay
in 10 second
increments,
x0 seconds
User Settings: From here one can enter the UPS
ID, adjust the contrast of the user interface LCD or
select the appropriate language.
User Settings
Set UPS ID
Screen Contrast
Display Language
Set UPS ID
Set UPS ID
xxxxxxxxxxxxxxx
xxxxxxxxxxxxxxx
Screen Contrast
Screen Contrast
Press
Press
Display Language
Display Language
English
Francais
Italiano
Deutsch
Espanol
Set Date/Time: Allows user to enable/disable DST
(Daylight Savings Time), change the Day, Date
and Time setting on Nfinity. When enabled, the
time will automatically adjust to Daylight Savings.
Set Time/Date
DST Mode
Set Time/Date
DST Mode
DST Mode
* Enabled
Disabled
Set Date/Time
Date/Time
MM/DD/YYYY
28
to Increase
to Decrease
HH:MM:SS