UPS Configuration Screen - Change Settings Menu

Starting at the Main Menu, select UPS Configuration and press
press
. Here one may configure Nfinity from a large variety of selections. Items with an asterisk (*) and
those that are underlined are the selected settings.
Main Menu
UPS Status
> UPS Configuration
Display Date/Time
Event Log
Alarm Log
Transfer to Bypass
Module Replacement
Tools
UPS Configuration
UPS Configuration
Review Settings
> Change Settings
Service Mode
Input Voltage L-N: Select the required input
voltage setting.
Input Voltage
230 LNE
* 240 LNE
Transformer Models
Input Voltage
230 LNE
220 LNE
* 240 LNE
Frequency Settings: Sets the input and output
operating frequency of the system.
Frequency Output
* 50 Hz
60 Hz
Frequency Sync Range: Sets the window to
which the system synchronizes to the input supply.
Frequency Sync Range
±0.5 Hz
±1.0 Hz
±2.0 Hz
±3.0 Hz
±4.0 Hz
* ±5.0 Hz
. Next, select Change Settings and
Change Settings
Change Settings
Input Voltage
Frequency
Freq Sync Range
Freq Slew Rate
Set Password
Auto Battery Test
Low Battery Warning
Auto Restart
User Settings
Set Time/Date
Max Load Alarm
UPS Shutdown Delay
Redund't Alarm Set
Service Contact
Remote Shutdown
External Battery
Bypass Alarm Mode
Intelli-Battery Cab
Air Filter Reminder
Factory Defaults
Frequency Slew Rate: Sets the rate of change of
frequency through the sync range window.
Frequency Slew Rate
0.5 Hz/S
1.0 Hz/S
2.0 Hz/S
3.0 Hz/S
4.0 Hz/S
* 5.0 Hz/S
Set Password: Set a Password to prevent
unauthorized users from changing the
configuration of the Nfinity. It can be up to 7
characters in length. Once set, the password will
be required to change the configuration.
Set Password
[xxxxxxx]
WARNING
If the password is lost, call Liebert Technical
Support.
27