9.0
S
PECIFICATIONS
The specifications of the Liebert GXT4 are listed in Table 13 and Table 14.
Table 13
Specifications of GXT4-700RT230/230E and GXT4-1000RT230/230E UPS
Parameters
Model Rating
Dimensions, D x W x H, mm (in)
Shipping
Weight, kg (lb)
Shipping
Input AC
Voltage Range (typical)
90% ~ 100% loading
70% ~ 90% loading
30% ~ 70% loading
0 ~ 30% loading
Frequency
Input Power Receptacle
Output AC
AC-AC Efficiency
Output Receptacles
Frequency
Waveform
Mains (AC) Mode Overload
Internal Battery Charger
Charger Current, Amperes
Battery
Qty × V× Rating
Battery Mfr/Part#
Backup Time
Recharge Time
Environmental Requirements
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
Agency
RFI/EMI
Surge Immunity
Transportation
GXT4-700RT230
GXT4-700RT230E
700VA/630W
Unit
Unit
Voltage
200% for 2 seconds; 150% for 50 seconds with transfer to bypass
Type
3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
0ºC to +40ºC (+32ºF to +104ºF); Table 16 - Operating temperature parameters
Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
Safety
IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A
Product model
408 x 430 x 85 (16.2 x 16.9 x 3.4)
617 x 570 x 262 (24.3 x 22.4 x 10.3)
18.2 (40)
24 (53); "E" model 20 (44)
230VAC nominal; variable based on output load
177VAC/280VAC
168VAC/280VAC
150VAC/280VAC
115VAC/280VAC
40Hz ~ 70Hz; Auto Sensing
C14
> 88% AC-AC, minimum
C13 × 6
200/208/220/230/240VAC (user configurable); ±3%
50Hz or 60Hz
Sine wave
1.3
Valve-regulated, nonspillable, lead acid
4 × 12V × 5.0Ah
YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
See Table 17 - Battery run times
(Internal Batteries Only)
-15ºC to +50ºC (5ºF to 122ºF)
0%RH to 95%RH, non-condensing
15,240 (50,000 ft.) maximum
< 46 dBA, at 1 meter (3.2ft) from the rear
< 43 dBA, at 1 meter (3.2ft) from the front or sides
IEC/EN/AS 62040-1:2008, GS mark; UL 1778 Listed
IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)
ISTA Procedure 1A
43