Setting The Correction Value For The External Radio Humidity Sensor; Selecting The Signal Source From Which The Actual Humidity Value Is Taken - Defensor H15A Service Manual

Adiabatic humidifiers
Table of Contents

Advertisement

2.2.3

Setting the correction value for the external radio humidity sensor

(see chapter 2.2.2)
Calibr. Radio
+01%rH Act:38%rH
(see chapter 2.2.4)
With this function you can determine a correction value, if the actual value of the external radio
humidity sensor deviates from the value of a certified humidity measuring instrument.
Note: Before the radio humidity sensor is calibrated or the correction value is determined, the radio
humidity sensor should have been some hours in the operation, so that the air around the sensor
can adapt itself to the ambient air.
Setting range:
Factory setting:
2.2.4

Selecting the signal source from which the actual humidity value is taken

(see chapter 2.2.3)
Act.Value Source
Internal
(see chapter 2.2.5)
With this function you can determine from which signal source the actual humidity value is taken.
Available settings:
Factory setting:
Calibr. Radio
New Value
Calibr. Radio
Old Value
-20 %rh ... +20 %rh
0 %rh
Act.Value Source
New Value
Act.Value Source
Old Value
Internal (internal humidity sensor)
Radio 1 (external radio humidity sensor channel 1)
Radio 2 (external radio humidity sensor channel 2)
Radio 3 (external radio humidity sensor channel 3)
Radio 4 (external radio humidity sensor channel 4)
Internal
modify
confirm
cancel
modify
confirm
cancel
7
Calibr. Radio
+01 %rH
- 20%rh ... + 20%rh
Act.Value Source
Internal
Intern, Radio 1, Radio 2,
Radio 3 or Radio 4