Settings In The Service Level; Viewing/Deleting The Error List; Setting The Correction Value For The Internal Humidity Sensor - Defensor H15A Service Manual

Adiabatic humidifiers
Table of Contents

Advertisement

6
2.2

Settings in the service level

2.2.1

Viewing/deleting the error list

(see chapter 2.2.8)
Error History
1/4/1/2
(see chapter 2.2.2)
With this function you can view the error list with the last 4 malfunctions occurred and if required,
delete the error list.
Note: The error list can give you important information for the elimination of malfunctions. Therefore
the error list should be deleted only, after a possible malfunction has been eliminated.
2.2.2

Setting the correction value for the internal humidity sensor

(see chapter 2.2.1)
Calibr. Internal
+02%rH Act:38%rH
(see chapter 2.2.3)
With this function you can determine a correction value, if the actual value of the integrated humidity
sensor deviates from the value of a certified humidity measuring instrument.
Note: Before the sensor is calibrated or the correction value is determined, the unit should have been
some hours in the operation, so that the air around the sensor can adapt itself to the ambient air.
Setting range:
Factory setting:
Delete error list:
press <Enter> key >3 seconds
Error History
Calibr. Internal
New Value
Calibr. Internal
Old Value
-20 %rh ... +20 %rh
0 %rh
modify
confirm
cancel
Calibr. Internal
+02 %rH
- 20%rh ... + 20%rh