Water Circuit; Positioning The Temperature Sensors - Beretta POWER MAX 50 P DEP Installation And Operation Manual

Power max series condensation, heating module
Hide thumbs Also See for POWER MAX 50 P DEP:
Table of Contents

Advertisement

1 9 Water circuit

5
4
3
2
RI
Heat exchanger
1
Circulator (only for models POWER MAX 50 P
2
DEP - POWER MAX 80 P)
Drain cock
3
Minimum pressure switch
4
NTC return probe
5
NTC delivery probe
6
Safety thermostat temperature sensor
7
Automatic bleed valve
8
Flow-meter
9
Central heating flow
MI
12
Central heating return
RI
Values of NTC probes' resistors with changing temper-
atures
Temperature
°C
Tolerance test
±10%
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
1
6 7 8
Temperature
Resistor
°C
Tolerance test
Ω
±10%
191908
45
146593
50
112877
55
87588
60
68471
65
53910
70
42739
75
34109
80
27396
85
22140
90
17999
95
14716
100
12099
105
10000
110
8308
115
6936
120
5819
125
1 10 Positioning the temperature
sensors
Probes placed on the related sockets of the thermal
module (POWER MAX 50 P DEP - POWER MAX 50 P):
Exhaust flue probe
1
Safety thermostat temperature sensor
2
CH flow temperature sensor
3
Return probe
4
9
MI
Front view
Probes placed on the related sockets of the thermal
module (POWER MAX 65 P ÷ POWER MAX 150):
Exhaust flue probe
1
Safety thermostat temperature sensor
2
CH flow temperature sensor
3
Return probe
4
Resistor
Ω
4904
4151
3529
3012
2582
2221
1918
1663
1446
1262
1105
970
855
755
669
594
529
Front view
3
2
4
1
Side view
3
2
4
1
Side view
1
3
2
1

Hide quick links: