NetAXS-123 Access Control Unit User's Guide
2.
3.
www.honeywell.com/security
Figure 2-28 Configuring Panel Inputs
Click to select an input.
Select Input Modes.
Configuration
Description
Normally
Normally Closed means that the input's normal state is closed.
(Default setting).
Normally Open means that the input's normal state is open.
State
Unsupervised means that the input's electrical circuit is wired in
one path without alternative paths supervised by resistors.
(Default setting)
Supervised means that the input's electrical circuit is wired in one
path with alternative paths supervised by resistors.
Resistor Value
Specifies the resistor values being used in the supervised modes.
Select from: 1K ohms, 2.2K ohms, 4.7K ohms, or 10K ohms. The
default is 2.2K.
Auto-Relock
Causes the door to re-lock immediately when the door status
switch closes after entry. The output relay that controls the door
strike de-energizes when the associated input returns to normal
state instead of remaining energized for the duration of the pulse
time. To enable Auto-Relock, de-select the Disable check box, and
select the associated output from the drop-down list.
Output
Select an Output value for Auto-Relock,