Section 5: Customizing Actuator Settings
February 2018
5.5.6
56
Relays #9 through #12 are the auxiliary relays when the Auxiliary Relay Module
(ARM) is installed. To configure these relay outputs, follow Step No.1 through
No. 3 listed above. See Table 5-3.
NOTE:
The ARM cannot be added when the Controlinc ACM is installed.
Table 5-3.
Relay Outputs #9 through #12 Configuration
Default
Relay
Function
RO#9
Lost Power
RO#10
Motor Overload
RO#11
Lost Phase
RO#12
Over Torque

Inhibit and ESD Setup

1.
At the "INHIBIT AND ESD SETUP?" prompt answer "YES."
2.
Use the selector knob (NEXT/BACK) to review the settings for Control
Inhibits and Emergency Shut Down.
3.
Use the control knob (NO) to select either ON or OFF for each setting;
then answer "YES."
Figure 5-11 details each setting.
Installation and Operation Manual
Configurable
Configure
Function
N.O./N.C.
See Table 5-2 Relay
Yes
Output Function List
See Table 5-2 Relay
Yes
Output Function List
See Table 5-2 Relay
Yes
Output Function List
See Table 5-2 Relay
Yes
Output Function List
E2K-405-0218 Rev. 2
Default
Setting
N.O.
N.O.
N.O.
N.O.
Customizing Actuator Settings