Enerzone Harmony 2.3 Installation And Operation Manual page 29

Table of Contents

Advertisement

APPLIANCE CLEARANCES (INSTALLATION
WITH SINGLE WALL PIPE CONNECTOR)
Canada
A
14 ½" (368 mm)
B
22" (559 mm)
C
12" (305 mm)
K
48" (1220 mm)
L
84" (213 cm)
If the above clearances are met, then the distances measured from the flue outlet will be:
DISTANCES
FROM PIPE CONNECTOR WITH
1
SINGLE WALL PIPE CONNECTOR
Canada
D
18" (457 mm)
E
31 ½" (800 mm)
F
21 ¾" (552 mm)
7.2.1 Clearances with heat shield AC02710
Note that to reduce the clearances of an appliance using a single wall pipe connector, the use
of a heat shield certified with the single wall pipe connector to be used as close as 6" from
combustible materials must be used. Only in this case, the same clearances as a certified
double wall pipe connector can be used.
APPLIANCE CLEARANCES (INSTALLATION
WITH DOUBLE WALL PIPE CONNECTOR)
Canada
A
3" (76 mm)
B
4" (102 mm)
C
3" (76 mm)
K
48" (122 cm)
L
84" (213 cm)
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances above
1
mentioned.
Installation and Operation Manual - Harmony 2.3
USA
11" (279 mm)
22" (559 mm)
12" (305 mm)
48" (1220 mm)
84" (213 cm)
USA
14 ½" (368 mm)
31 ½" (800 mm)
21 ¾" (552 mm)
USA
3" (76 mm)
4" (102 mm)
3" (76 mm)
48" (122 cm)
84" (213 cm)
APPLIANCE CLEARANCES (INSTALLATION
WITH DOUBLE WALL PIPE CONNECTOR)
Canada
A
6" (152 mm)
B
22" (559 mm)
C
12" (305 mm)
K
48" (1220 mm)
L
84" (213 cm)
DISTANCES
FROM PIPE CONNECTOR WITH
1
DOUBLE WALL PIPE CONNECTOR
Canada
D
9 ¼" (235 mm)
E
31 ¼" (794 mm)
F
21 ½" (546 mm)
DISTANCES
FROM DOUBLE WALL PIPE
1
CONNECTOR
Canada
D
6 ¼" (159 mm)
E
13 ¼" (337 mm)
F
12 ½" (318 mm)
USA
6" (152 mm)
22" (559 mm)
12" (305 mm)
48" (1220 mm)
84" (213 cm)
USA
9 ¼" (235 mm)
31 ¼" (794 mm)
21 ½" (546 mm)
USA
6 ¼" (159 mm)
13 ¼" (337 mm)
12 ½" (318 mm)
Page 29