3-2-10 Connection Locations For Communications Power Supply - Omron CS1W-CRM21 Operation Manual

Componet master units
Table of Contents

Advertisement

CompoNet Network Wiring

3-2-10 Connection Locations for Communications Power Supply

Round Cable II, Flat Cable
I, or Flat Cable II
Note
Round Cable I
58
Connect the communications power supply as shown in the following dia-
grams.
Example for Flat Cable I or II
Communica-
tions power
supply, 24 VDC
+
Master Unit
Com-
muni-
cati-
ons
power
supply
Communications
connector
The communications power supply (BS+ and BS-) is connected to the com-
munications power supply connector on the Master Unit. Doing so will supply
communications power to the Slave Units on the trunk line from the Round
Cable II, Flat Cable I, or Flat Cable II.
(1) Connect the communications power supply at only one location for the
trunk line and each sub-trunk line.
(2) Connect the communications power supply to the downstream port com-
munications power supply connector on the Repeater Unit to supply pow-
er to a sub-trunk line.
Communica-
tions power
supply, 24 VDC
+
Master Unit
Open Type Connector
Round Cable I
Communications connector
Normal Slave Unit
The communications power supply (BS+ and BS-) is connected separately to
each Slave Unit and Repeater Unit (see note). Power does not need to be
supplied to the Master Unit.
Note The communications power to the Repeater Unit must be supplied
to the BS+ and BS- terminals on the upstream port (port 1).
Refer to 4-4 Power Supply Wiring for details on wiring the communications
power supply.
Flat Cable I or II
Slave Unit
Slave Unit
Supply communications power directly to each Slave Unit.
Open Type Connector
Open Type Connector
Normal Slave Unit
Section 3-2
Terminating Resistor
Slave Unit
Terminating Resistor
Open Type Connector
Normal Slave Unit