Delta AG9064 Installation Manual page 21

Delta networking – agema family spine switch
Table of Contents

Advertisement

b. Adapter connector for DC source connection
1. Attach the connector directly into the DC socket of a PSU located at the back of the switch.
(Figure 3-10: Assembling a DC Connector and Power Wires)
2. Plug the other end of power wires into DC power source. This product is intended to be
supplied by DC power source with rated -36V - -72Vdc, 42A minimum, Tma = 45 degree C,
and the altitude of operation = 5000 m. The power cable should be 14AWG (42A minimum,
-36V minimum).
CAUTION:
MISE EN GARDE:
3. Check the PSU and front-panel LEDs as the device is powered on to be sure that DC
power is being received and the PWR1 LED is on. If not, check that the power cable is
correctly plugged in.
4. Repeat steps 1 and 2 when a second PSU module is installed.
Two installed PSU modules operate in a load-sharing mode and provide 1+1 redundancy.
Reversing polarity when connecting DC power wires can
permanently damage the power supply or the system.
Always disconnect the power cable from power source before you
service the power supply slots.
L'inversion de la polarité des câbles d'alimentation CC lors de
leur branchement peut endommager irréversiblement le bloc
d'alimentation ou le système.
Débranchez le câble d'alimentation de l'unité d'alimentation avant
l'entretien des fentes du bloc d'alimentation.
17
Chapter 3
• Installation
-48V_RTN (+DC)
GND
-48V(-DC)

Advertisement

Table of Contents
loading

Table of Contents