Summary of Contents for Delta STS30002SR00035

  • Page 1 S2- ON RE SE S1- ON NE TW OR K LO CA S2- ON RE SE S1- ON NE TW OR K LO CA S2- ON The power behind competitiveness Delta Infrasuite Power Management Rack Static Transfer Switch User Manual www.deltapowersolutions.com...
  • Page 2 Failure to heed these instructions and warnings will void the warranty. Copyright © 2022 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc.
  • Page 3: Table Of Contents

    Package List ------------------------------------------------------ 3 Features ----------------------------------------------------------- 4 Model Type -------------------------------------------------------- 5 Chapter 3 : Installation ----------------------------------------------------- 7 Installation_ Model: STS30002SR00035 ------------------ 7 Installation_ Model: STS30002SR10035 ------------------ 8 Installation_ Model: STS30002SR10135 ------------------ 9 Chapter 4 : Wiring ----------------------------------------------------------10 Wiring_ Model: STS30002SR00035 -----------------------10...
  • Page 4 SNMP IPv6 Features ------------------------------------------18 Top View and Front View of SNMP IPv6 -----------------19 Console Management -----------------------------------------20 Upgrade -----------------------------------------------------------24 rSTS Command Settings -------------------------------------26 Key Generation for SSH --------------------------------------30 Chapter 8 : Troubleshooting --------------------------------------------32 Appendix 1 : Specifications ---------------------------------------------33 Appendix 2 : Warranty ----------------------------------------------------34 Infrasuite Power Management...
  • Page 5: Chapter 1 : Important Safety Instructions

    7. Do not operate the unit close to gas or fire. Upstream circuit breaker must be added for each input. The recommended break- er is D curve 30A for STS30002SR00035 and D curve 32A for STS30002SR10035 and STS30002SR10135. Verify whether the branch circuit breaker or fuse on service feed is correct.
  • Page 6: Standard Compliance

    1.3 Standard Compliance Safety UL (US) : UL 62368-1 (only for STS30002SR00035) CE (EU) : IEC/EN 62368-1 CISPR 22 Class A and FCC Class A IEC 61000-4-2 IEC 61000-4-6 IEC 61000-4-3 IEC 61000-4-8 IEC 61000-4-4 IEC 61000-4-11 IEC 61000-4-5 IPv6 Certification IPv6 Ready Logo Phase 2 (Core for Host, Logo ID 02-C-000624) 1.4 Storage...
  • Page 7: Chapter 2 : Introduction

    2.2 Package List S1- ON S1- ON NE TW OR K NE TW OR K LO CA LO CA S2- ON S2- ON RE SET STS30002SR00035 STS30002SR10035 S1- ON NE TW OR K LO CA S2- ON RE SET STS30002SR10135...
  • Page 8: Features

    Item Q’ty 1 PC rSTS 2 PCS Bracket Ear 8 PCS Bracket Screw 4 PCS Rack Screw 4 PCS Rack Nut NOTE : 1. If there is any damage or anything missing, please immediately contact the dealer from whom you purchased the unit. 2.
  • Page 9: Model Type

    3600 mm 450 mm STS30002SR00035 L6-30P L6-30R (141.73'') (17.72'') 4000 mm 1000 mm STS30002SR10035 IEC309-32A IEC309-32A (39.37'') (157.48'') HP-T4049S- HP-T4049S- STS30002SR10135 3P-L2 3P-L2 Model: STS30002SR00035 S1 -O NE TW OR K TE ST LO CA O/ P S2 -O RE SE...
  • Page 10 Model: STS30002SR10035 S1 -O NE TW OR K TE ST LO CA O/ P S2 -O Model: STS30002SR10135 S1 -O NE TW OR K TE ST LO CA O/ P S2 -O RE SE Infrasuite Power Management...
  • Page 11: Chapter 3 : Installation

    Chapter 3 Installation Chapter 3 : Installation 3.1 Installation_ Model: STS30002SR00035 Front installation S1-ON NETW ORK LOCA L RESE T TEST S2-ON Rear installation NETW ORK S1-O N LOC AL RES ET TEST S2-O N NOTE : After installation, the surplus four bracket screws, two rack nuts...
  • Page 12: Installation_ Model: Sts30002Sr10035

    3.2 Installation_ Model: STS30002SR10035 Front installation NETW ORK S1-ON LOCA L RESE T TEST S2-ON Rear installation NETW ORK S1-O N LOC AL TEST RES ET S2-O N NOTE : After installation, the surplus four bracket screws, two rack nuts and two rack screws are spare parts.
  • Page 13: Installation_ Model: Sts30002Sr10135

    Chapter 3 Installation 3.3 Installation_ Model: STS30002SR10135 Front installation NET WOR S1-O N LOC AL RES ET TES T S2-O N Rear installation NET WOR S1-O N LOC AL TES T RES ET S2-O N NOTE : After installation, the surplus four bracket screws, two rack nuts and two rack screws are spare parts.
  • Page 14: Chapter 4 : Wiring

    Chapter 4 : Wiring 4.1 Wiring_ Model: STS30002SR00035 Connect the input power cables (provided) to two power sources (source 1 (S1) & source 2 (S2)). Source 1 (S1) is the preferred source. Connect the output power cable (provided) to your load.
  • Page 15: Wiring_ Model: Sts30002Sr10135

    Chapter 4 Wiring S1 -O NE TW OR K TE ST LO CA O/ P S2 -O RE SE 4.3 Wiring_ Model: STS30002SR10135 Remove the two screws shown in the figure below. O /P...
  • Page 16 After removing the two screws, you will see the wiring terminals (L, N, G) as follows. O /P Follow the following table to use the specified wires to connect the wiring terminals and the source 1 (S1), source 2 (S2) and your load. For wiring, please refer the figure below.
  • Page 17: Chapter 5 : Front Panel

    Chapter 5 Front Panel Chapter 5 : Front Panel NETWORK LOCAL RESET S1-ON TEST S2-ON Item Description Green. The LED indicates the condition of input source 1. If the input source 1 is within the acceptable range, the S1 LED LED will light up as green.
  • Page 18 Item Description Green. If you press the test button, the rSTS will be under Test test and the Test LED will flash (on: 0.5s; off: 0.5s). In normal operation, the LED will be off. Red. If the rSTS has any internal fault, the LED will light up as red.
  • Page 19 Chapter 5 Front Panel Item Description NETWORK Connects to the Ethernet Network. Port LOCAL Connects to a workstation with an RJ45 to DB9 cable to Port configure the system. Resets InsightPower SNMP IPv6 for rSTS (hereafter referred RESET to as SNMP IPv6). This DOES NOT affect the operation of Button the rSTS.
  • Page 20 Item Description Set up operation mode. Please refer to the following table. DIP Switch 1 DIP Switch 2 Operation Description Switch 1 Switch 2 Mode The built-in SNMP IPv6 provides the rSTS’s Normal status information and Mode parameters through a network system.
  • Page 21: Chapter 6 : Operation

    Chapter 6 Operation Chapter 6 : Operation 2 poles circuit breaker rSTS (L1) (N1) (Source 1) To the sensitive equipment 2 poles circuit breaker (L2) (N2) (Source 2) After power connection, the rSTS will automatically perform power-on self-test. After the test, the rSTS will start supplying power to its connected equipment. You can also press the Test Button to force the rSTS to execute self-test.
  • Page 22: Chapter 7 : Insightpower Snmp Ipv6 For Rsts

    Allows remote management of the rSTS from any workstation through Internet or Intranet. Remote rSTS monitoring via SNMP & HTTP Allows remote monitoring of the rSTS using SNMP NMS, Delta MIB (Management Information Base) or a Web Browser. rSTS and system function configuration from any client (password pro- tected) Sets the rSTS and system parameters through a Web Browser.
  • Page 23: Top View And Front View Of Snmp Ipv6

    Chapter 7 InsightPower SNMP IPv6 for rSTS - BOOTP/ DHCP - HTTPS, SSH, SFTP and SNMPv3 security protocols - RADIUS (Remote Authentication Dial In User Service) login and local authentication - Remote event log management through syslog - IPv6 Ready Logo certified (ID 02-C-000624) DEFAULT SETTING User Name: admin Password: password...
  • Page 24: Console Management

    7.4 Console Management You can manage the SNMP IPv6 through the LOCAL port. Please use an RJ45 to DB9 cable to connect the SNMP IPv6’s LOCAL port and your workstation’s COM port. Make sure both of the DIP switches are set to the OFF position (normal mode). The baud-rate of the workstation’s COM setting should be 2400 bps.
  • Page 25 Chapter 7 InsightPower SNMP IPv6 for rSTS TCP/ IP Setting +========================+ TCP/IP Setting +========================+ [1].IPv4 Address: 192.168.1.100 [2].IPv4 Subnet Mask: 255.255.255.0 [3].IPv4 Gateway IP: 192.168.1.254 [4].IPv4 DNS or WINS IP:192.168.1.254 [5].DHCPv4 Client: Enable [6].IPv6 Address: [7].IPv6 Prefix Length: 0 [8].IPv6 Gateway IP: fe80::226:Sbff:fecc:fdal [9].IPv6 DNS IP: [a].DHCPv6:...
  • Page 26 Time Server +========================+ Time Server +========================+ [1].Time Selection: SNTP [2].Time Zone: +0 hr [3].1st Time Server: [4].2nd Time Server: [5].Manual Date: 01/01/2000 (MM/DD/YYYY) [6].Manual Time: 00:00:00 (hh:mm:ss) [0].Back To Previous Menu Please Enter Your Choice => Soft Restart +========================+ Web Card Main Menu +========================+ Web Card Version 01.12.11f MAC Address 00-30-ab-26-b1-b4...
  • Page 27 Chapter 7 InsightPower SNMP IPv6 for rSTS Device Communication You can enter the rSTS Command Mode below by selecting Device Communi- cation. STS> Vs1 216.8 STS> Vs2 217.9 STS> Iout STS> Vout 217.1 STS> Vbp2s 180.0 STS> Vbs2p 180.0 STS> Tdp2s 12.0 STS>...
  • Page 28: Upgrade

    7.5 Upgrade Upgrade via Web You can upgrade the SNMP IPv6’s firmware or the rSTS’s firmware through the InsightPower SNMP IPv6 for rSTS Web (please see the following figure). The SNMP IPv6 will restart after finishing self-upgrade. If you upload the rSTS’s firmware to the Web, you can see the rSTS’s firmware upgrade progress from the Web.
  • Page 29 Chapter 7 InsightPower SNMP IPv6 for rSTS Upgrade via EzSetting You can also upgrade the SNMP IPv6’s firmware or the rSTS’s firmware by using EzSetting. 1. Click Discover. A list of SNMP devices is shown. Select a device from the Device List, and click Modify.
  • Page 30: Rsts Command Settings

    3. Click Upgrade. The upgrade dialog box pops up. Click Browse to select a valid firmware binary file. Verify the firmware version shown under File Information, and then click Upgrade Now to continue. 7.6 rSTS Command Settings Command Description Parameter Response Info Report summary information.
  • Page 31 Chapter 7 InsightPower SNMP IPv6 for rSTS Command Description Parameter Response Prefer Report the preferred source. S1 or S2 Sens Report the sensitivity. hi or low Initialization Diagnosis Mode Report the operation mode. Safe Fault 1- normal/ Check current MODBUS Link 2- abnormal/ connection.
  • Page 32 Report the recovery time of Tds2p transfer from secondary to primary. Report the max voltage of Mvs1 comparing cycles for primary AC blackout. Report the max voltage Mvs2 of comparing cycles for secondary AC blackout. Report the max time of Mts1 comparing cycles for primary AC blackout.
  • Page 33 Chapter 7 InsightPower SNMP IPv6 for rSTS LogM Report monthly log. <List of monthly log> [Index | Month] [1-200] Setting hh:mm:ss SetTime Set the present time. [Message] [MM/DD/YYYY] SetDate Set the present date. MM/DD/YYYY [Message] SetPrefer Set the preferred source. 1 or 2 [Message] <20 characters>...
  • Page 34: Key Generation For Ssh

    Upgrade Status UpProcess Status of upgrade progress. Idle / Run / Error Init/ FileID/ Auth/ Addr/ Erase/ UpStep Stage of upgrade progress. Program/ Read Percentage of upgrade UpPercentage progress. OK/ No response/ File ID fail/ Authenticate fail/ Erase fail/ UpResult Result of upgrade progress.
  • Page 35 Chapter 7 InsightPower SNMP IPv6 for rSTS (3) Upload DSA and RSA key files on the web. For Windows (1) Please download and install PuTTY from http://www.putty.org. (2) Run puttygen.exe from the installed directory. (3) Select SSH-2 RSA from the Parameters area and click Key→ Generate key pair to generate an RSA key.
  • Page 36: Chapter 8 : Troubleshooting

    Chapter 8 : Troubleshooting Problem Possible case Solution 1. Check the output (overload/ short-circuit). The power All LEDs on the sources, S1 and 2. Check both power sources, S1 front panel are off. S2, are both and S2. absent. 3. Reset the upstream circuit breakers.
  • Page 37: Appendix 1 : Specifications

    Specifications Appendix 1 : Specifications rSTS Operating 200/208/220/230/240 Vac Voltage Operating 45 ~ 65 Hz Frequency STS30002SR00035 24A for UL/25.6A for CE Current Rating STS30002SR10035 30A* STS30002SR10135 30A* 43 × 440 × 385 mm STS30002SR00035 (1.69'' × 17.32'' × 15.16'') Physical 43 ×...
  • Page 38: Appendix 2 : Warranty

    Appendix 2 : Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty period, Seller will repair or replace the product at its sole discretion according to the failure situation.
  • Page 39 - Regional Office The United States Australia Delta Electronics (Americas) Ltd. Delta Energy Systems Australia Pty Ltd. 46101 Fremont Blvd. Fremont, CA 94538 Unit 20-21, 45 Normanby Road, Notting Hill VIC 3168, Australia T +1 510 344 2157 T +61 3 9543 3720 E ups.na@deltaww.com...
  • Page 40 5013212303...