5-3-5 I/O Module Calibrations
Calibration is to adjust the accuracy of ADAM module. There are several modes for module's calibration:
Zero calibration, Span calibration, CJC calibration, and Analog Output calibration. Only analog input and
output modules can be calibrated, and the ADAM-6017 is the first released analog module.
Zero Calibration
1. Apply power to the module and let it warm up for 30 minutes.
2. Make sure the module is correctly installed and properly configured for the input range you want to
calibrate.
3. Use a precision voltage source to apply a calibration voltage to the V+ and V- terminals of the
ADAM-6017 module.
4. Click the Execute button.
Span Calibration
Follow the same procedure of zero calibration and click the Execute button.
Figure 5-21 Zero Calibration
Figure 5-22 Span Calibration