Function Code 16 (10 hex)
Preset values into a sequence of holding registers.
Request message format for function code 16:
Station
Function
Start Address
Address
Code
High Byte
Example: Preset constant #1 (address 40009) to 100.0 in ADAM-6000 module.
01 10 00 09 00 02 04 42 C8 00 00
Response message format for function code 08:
The normal responses return the station address, function code, start address, and requested number of
registers preset.
Station
Function
Start Address
Address
Code
High Byte
Example: 01 10 00 09 00 02