Parameter
Description
19 HOn
Setting the ON hysteresis for heating or
cooling requests.
The value can be set from 0°C to 2°C; the
default setting is 0.4°C.
RiCLOUD processes an ON request below the
target room temperature set (desired room
setpoint – H On) if the heating mode is active,
or above the target room temperature set
(desired room setpoint + H On) if the cooling
mode is active.
19 HOFF
Setting the OFF hysteresis for heating or
cooling requests.
The value can be set from 0°C to 2°C; the
default setting is 0.1°C.
RiCLOUD processes an OFF request above the
target room temperature set (desired room
setpoint + H OFF) if the heating mode is
active, or below the target room temperature
set (desired room setpoint – H OFF) if the
cooling mode is active.
21 ALL
Alarm history display (available with OTBus
connection between the WiFi Box and the
boiler or the RF receiver and the boiler or
RiCLOUD and the boiler, if provided for by the
OTBus protocol). The last 9 alarms generated
by the boiler and saved by RiCLOUD are
shown.
22 tSP
Setting boiler parameters (available with
OTBus connection between the WiFi Box and
the boiler or the RF receiver and the boiler or
RiCLOUD and the boiler, if provided for by the
OTBus protocol). This parameter is set by the
Authorised Service Centre.