Riello RiCloud User Manual page 34

Hide thumbs Also See for RiCloud:
Table of Contents

Advertisement

Parameter
100
80
60
40
20
20
16
T Mand risc = T Mand Curva + ( CLI * InFL * ΔT Amb)
T Mand Curva = Delivery temperature calculated using the
thermoregulation curve set under parameter CLI
CLI = thermoregulation curve
InFL = room influence
ΔT Amb = (room temperature set) – (current room temperature)
11 InFL
T Mand risc= T Mand Curva + ( CLI * InFL * ΔT Amb)
T Mand Curva = Delivery temperature calculated using the
thermoregulation curve set under parameter CLI
CLI = thermoregulation curve
InFL = room influence
ΔT Amb = (room temperature set) – (current room temperature)
9
Setting the parameter InFL=0, with the external probe disconnected
from the boiler and the web external probe not enabled on the app,
the heating delivery temperature
is the same as the temperature set under parameter LLCH.
12
8
4
0
Influence of room probe on calculation
of heating delivery setpoint temperature
(available with OTBus connection between
the WiFi Box and the boiler or the RF receiver
and the boiler or RiCLOUD and the boiler, if
provided for by the OTBus protocol).
Default set to 10.
The value can be set from 0°C to 20°C.
81
Description
3
2,5
-4
-8 -12 -16
(per la zona comandata dal RiCLOUD)
2
1,5
1,2
1
0,8
0,6
0,4
0,2