Step Voltage Test - AEMC 5100 User Manual

5000v megohmmeter
Table of Contents

Advertisement

Megohmmeter Models 5000N/5100/5110

Step Voltage Test

Method
In this test, the operator applies two or more test voltages in steps. The
recommended ratio for the test voltage steps is 1 to 5. At each step, test
voltage should be applied for the same length of time, usually 60
seconds. The application of increased voltage creates electrical stresses
on internal insulation cracks. This can reveal aging and physical
damage, even in relatively dry and clean insulation, which would not
have been apparent at lower voltages.
Test Duration
A series of "steps," each step lasting 60 seconds.
Interpreting the Results
Compare the readings taken at different voltage levels, looking for any
excessive reduction in insulation resistance values at the higher voltage
levels. Insulation that is thoroughly dry, clean, and without physical
damage should provide roughly the same resistance values despite
changes in test voltage levels. If resistance values decrease substantially
when tested at higher voltage levels, this should serve as a warning that
insulation quality may be deteriorating due to dirt, moisture, cracking,
aging, etc.