Utilizing the Guard Terminal

Guard terminals are useful when measuring high resistance values and
for stabilizing readings.
A
When testing the insulation at the end of a cable, it is necessary to
eliminate the error from surface leakage that occurs, particularly at high
resistance values. The guard terminal provides a third terminal within the
path of the surface leakage. Connect the instrument as shown in Figure
7.
If there is no shield at "B", use a copper wire wound several times around
the exposed surface "B". (Note: If a shield is not available and you do
not make up a shield around "B" and connect to the guard terminal (-),
the measurement will be erroneous and lead to confusion as to the
cable's state).