15.5 Information on insulation tests, protection class, degree of protection and rated voltage

Climatic ambient conditions
The following table shows the permissible climatic ambient conditions for the S7-1500
automation system/ET 200MP distributed I/O system:
Table 15- 9
Climatic ambient conditions
Ambient conditions
Temperature:
horizontal mounting
position:
vertical mounting position:
Temperature variation
Relative humidity
Barometric pressure
Pollutant concentration
15.5
Information on insulation tests, protection class, degree of protection
and rated voltage
Insulation
The insulation is designed in accordance with the requirements of EN 61131-2: 2007.
Note
For modules with 24 V DC supply voltage, the galvanic isolation is designed for max.
60 V AC/75 V DC and basic insulation is designed according to EN 61131-2: 2007 .
Pollution degree/overvoltage category according to IEC 61131-2: 2007
● Pollution degree 2
● Overvoltage category: II
Protection class according to IEC 61131-2: 2007
Protection class I or III, depending on module type
Automation system
System Manual, 12/2014, A5E03461182-AC
Permissible range
0 °C to 60 °C
0 °C to 40 °C
10 K/h
from 10 % to 95 %
from 1080 hPa to 795 hPa
SO
: <0.5 ppm;
2
RH <60%, no condensation
H
S: < 0.1 ppm;
2
RH < 60 %, no condensation
ISA-S71.04 severity level G1; G2; G3
Comments
To increase the service life of the display, the
display switches off when the permitted operating
temperature is exceeded.
Further information about the temperatures at
which the display switches off and back on again is
available in the technical specifications of the
manuals of the CPUs.
-
Without condensation, corresponds to relative
humidity (RH) class 2 in accordance with
IEC 61131 part 2
corresponds to an altitude of -1000 m to 2000 m
-
-
Technical specifications