Configuring And Programming Configuration Control - Siemens SIMATIC S7-1500 System Manual

Automation system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Flexible automation concepts
9.2 Configuration control
Error messages
The following error messages are returned if an error occurs during reading of the feedback
data record:
Table 9- 9
Error code
80B1
80B5
80B8
9.2.5

Configuring and programming configuration control

Requirements
For S7-1500 automation system:
● STEP 7 Professional Version V13 or higher
● CPU S7-15XX as of firmware version V1.5
● The startup parameter "Compare preset to actual configuration" is set to "Startup CPU
even if mismatch" (default setting).
For ET 200MP distributed I/O system:
● STEP 7 Professional Version V13 or higher
● IM 155-5 PN ST/HF
● The startup parameter "Comparison preset to actual module" is set to "Startup CPU even
if mismatch" (default setting).
● You have assigned the interface module to an IO controller/DP master in STEP 7
134
Error messages
Meaning
Invalid length; the length information in data record 197 is not correct.
H
Configuration control not configured
H
Parameter error
H
The following events cause a parameter error:
Incorrect block ID in the header (not equal to 197)
Invalid version identifier in the header
A reserved bit was set
Multiple slots in the station master are assigned to the same slot in the station
option
Automation system
System Manual, 12/2014, A5E03461182-AC