Configuring
6.1 Configuring the CPU
Procedure
To upload CPU to your project, follow these steps:
1. Select the project name in the project tree.
2. In the "Online" menu, select the "Upload the device as new station (hardware and
software)".
The "Upload device to PG/PC" dialog is opened.
3. Choose required interface type in the "Type of PG/PC interface" drop-down list.
4. Select the interface to be used from the "PG/PC interface" drop-down list.
5. Click the "Configure interface" button to the right of the "PG/PC interface" drop-down list
to adapt the settings for the selected interface.
6. Display all compatible devices by selecting the relevant option and clicking the "Start
search" command. In the accessible devices table, select the device from which you want
to upload project data.
7. Click "Load".
6.1.4.5

Snapshot of the monitor values

Backing up actual values of all data blocks
With the option "Snapshot of the monitor values" you overwrite the start values of tags in the
offline version of a data block with actual values from the CPU. In this way, you can restore
the backed up status of the data blocks at a later date after changing the actual values.
To apply the actual values, you first generate a snapshot of tag values from the online
program. You can then apply these as start values.
Note
Note that the values from the snapshot are always copied. STEP 7 does not hereby check
whether all values originate from the same cycle.