Step 2: Attaching the MicroGTs to the PV Frame/Rack

1. Mark the location of each MicroGT 500 inverter on the PV rack—
keep in mind the location of the AC branch circuit junction box,
or any other obstructions.
2. Mount and attach a MicroGT inverter at each of the identifi ed
locations using hardware recommended by the PV module
racking vendor (Figure 5).
Note: If you are using the appropriate grounding washer (check with
an electrician), place the grounding washer (WEEB) between the PV
racking frame and the MicroGT 500 inverter.
WARNING: Prior to installing any MicroGTs, verify that the
utility voltage at the point of common connection matches
the voltage rating on the MicroGT inverter's label.
WARNING: Do not mount the MicroGT inverter in a location
that allows exposure to direct sunlight. Leave a minimum
of 3/4" (1.5 cm) between the roof and the bottom of the
MicroGT inverter to allow proper air fl ow.
Note: Connecting cables (Steps 3-5) can be done in any order, but
DO NOT energize until all the steps are completed.
4" (101 mm)

Figure 5, Attaching MicroGTs to the PV Module Frame