Display
AU
OP
CPU
Note) Refer to "Troubleshooting (1) and (2)" on pages 76 and 78.
75
Downloaded from
www.Manualslib.com
Details and cause of faults
•
An auxiliary stop signal was
input from control circuit
terminal
•
The power was turned ON while
the run signal was ON
•
The run signal was turned ON
while setting data in the
stopped mode, or the mode
was returned to the operation
mode with the MODE button
•
Excessive noise was applied
on the inverter
manuals search engine
Remedies
•
Check the sequence circuit to
confirm that the auxiliary stop
signal is correct.
•
Check the power loss start mode
(parameter P48)
•
Check the run signal when the
data is being set
•
Reduce the noise around the
inverter