0V Stop Function; Resetting Fault Trips - Panasonic VF0 Series Instruction Manual

Compact inverter 400v class
Hide thumbs Also See for VF0 Series:
Table of Contents

Advertisement

If the frequency setting signal is a command (panel potentiometer, external
potentiometer, 0 to 5V, 0 to 10V, 4 to 20mA) other than the "digital setting
with operation panel (parameter P09 = 1)", the inverter will start and stop at
a boundary of approx. 1/100 of the input signal's full scale using the factory
set data.
∗ 0V stop will not take place if the bias/gain function selection (parameter P55) is set to
If a fault is displayed on the operation panel's display and the inverter is
stopped, remedy the fault before resetting.
73
Downloaded from
www.Manualslib.com

0V Stop Function

"1", and the bias frequency (parameter P56) is set to "0.1" or more.
Frequency setting signal
Max, 5V, 10, 20mA
Min, 0V, 0V, 4mA
Run signal
Maximum output frequency
Output frequency
A, B indicate 0V stop
state

Resetting Fault Trips

Power reset
Turn OFF the power once, then turn it ON again.
(Operation can be started when the power is turned ON again.)
Resetting by
(1) When operation is set to local (Parameter P09 set to "0" or "1")
stop signal
The fault will be reset when the "STOP button" on the operation panel is
pressed. Operation can be restarted after this.
(2) When operation is set to external (Parameter P09 set to "2" or "3")
The fault will be reset when the "run command switch" is turned OFF
from the external source. Operation can be restarted after this.
Resetting by
(1) When operation is set to external (Parameter P09 set to "4" or "5")
panel
The fault will not be reset even if the "run command switch" is turned
OFF from an external source.
The fault will be reset when the "STOP button" on the operation panel is
pressed. Operation can be restarted after this.
Multi-function
(1) When setting data is set to "1" for parameters P19, P20 and P21
terminal reset
The fault will be reset when the switch set for the function is turned "ON"
and "OFF". Operation can be restarted after this. (Refer to page 68.)
manuals search engine
[When P55 = 0, or P55 =
1, P56 = 00.0 or less]
100%
Approx. 1%
0
B
A
[When P55 = 1, and
P56 = 00.1 or more]
100%
Approx. 1%