INNCOM E7 THERMOSTAT USER GUIDE

SETUP FAN SPEED

Once FAN is displayed, press MODE. Then use the UP/DOWN arrow
1.
buttons to choose the fan speed:
00: Not Defined
Lo: Low Speed (single speed)
LH: Low / High
LMh:Low / Medium* / High
*For heat pump models utilizing reversing valve, medium heat and
medium fan speed will not be available.
Press FAN to execute the setting, the unit beeps to confirm it is set.
2.

Exit Initialization Mode

When setup is complete, exit INITIALIZATION MODE by pressing the
key.
is displayed, indicating the setup values are stored in memory, the unit
Str
reboots and begins operating the HVAC equipment as configured.

Resetting Initialization Mode

If the user needs to return to the settings made in INITIALIZATION MODE, do
the following:
Enter SERVICE MODE:
1.
(1) Press and hold
(2) Press and hold MODE.
(3) Press and hold FAN.
o
o
(4) Release
F|
C.
Use the UP/DOWN arrow buttons to display
2.
Use the DOWN button to select
3.
Press FAN.
4.
The unit will reset, clear all previous values, and enter INITIALIZATION MODE again.
5.
36-00013—02
o
o
F|
C.
rst,
.
255
o
o
F|
C
then press MODE.