ABB RPBA-01 User Manual page 86

Profibus dp adapter module
Table of Contents

Advertisement

86
16h
Parameter address
impermissible
17h
Illegal format
18h
Number of values inconsistent
65h ...
Manufacturer-specific
FF
65h
Vendor-specific error
66h
Request not supported
67h
Communication error
68h ...
Manufacturer-specific
6Dh
6Eh
Non-volatile error
6Fh
Time-out error
70h ...
Manufacturer-specific
77h
78h
PZD map failure
79h
PZD memory failure
7Ah
Multiple PZD map
7Bh ...
Manufacturer-specific
81h
82h
Control word bit map
DP-V1 communication
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Illegal value or value that is not
supported for the attribute, number of
elements, parameter number or sub-
index, or a combination
Write request: Illegal format or format of
parameter data that is not supported
Write request: Number of values of
parameter data does not match number
of elements at the parameter address
Vendor-specific error
Request not supported
Request cannot be completed because
of communication error
Failure during write to non-volatile
memory
Request aborted because of timeout
Parameter cannot be mapped to PZD
(size mismatch or non-existent)
Parameter cannot be mapped to PZD
(out of memory)
Parameter cannot be mapped to PZD
(multiple PZD write)
Cannot map Control word bit
(parameter 933...937, e.g. double
mapping of bits)