• Set the PPO type, baud rate and node number.

Mechanical and electrical installation

• Set the node address using the rotary switches on the module.
(If the node address is set by software, set the switches to the
"0" position.)
• Set the bus termination switch to the desired position.
• Insert the RPBA-01 into its specified slot in the drive (SLOT2 for
ACS550, SLOT1 for ACS800).
• Fasten the two screws.
• Plug the fieldbus connector to the module.

Drive configuration

• Power up the drive.
• The detailed procedure of activating the drive for
communication with the module is dependent on the drive type.
Normally, a parameter must be adjusted to activate the
communication. Refer to the Firmware Manual of the drive for