information on the communication settings. With an ACS550
drive, set parameter 98.02 COMM. MODULE LINK to EXT FBA.
With an ACS800, set parameter 98.02 COMM. MODULE LINK
to FIELDBUS and parameter 98.07 COMM PROFILE to ABB
DRIVES or GENERIC (according to PLC hardware
configuration).
• If the configuration is correct, parameter group 51 should
appear in the parameter list of the drive and show the status of
the bus configuration parameters.
• If the node address is to be set by software, set the required
address at parameter 51.02 NODE ADDRESS.
Quick start-up guide