Example 1: Reading a drive parameter (or data set)
To determine the parameter number and subindex for drive
parameter reading, multiply the parameter number by one
hundred and then convert it to hexadecimal. The low byte is the
subindex (IND), and the high byte is the parameter number (PNU).
For example reading parameter 84.11 INPUT 1 from the drive:
84.11 × 100 = 8411 = 20DBh.
Parameter number is 20 and subindex is DB.
Request (Read parameter value [array])
Parameter Number (20h)
Req 60 20 DB 00 00 00 00 00 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 40 20 DB 00 00 00 00 64 03 37 34 15 00 00 00 00 00 00 00 00