ABB RPBA-01 User Manual page 66

Profibus dp adapter module
Table of Contents

Advertisement

66
8
9
DP-V1 communication
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
DPV1_Status_2
x x x x x x 0 x
MSB
DPV1_Status_3
0 0 0 x x x x x
MSB
LSB
Chk_Cfg_Mode
0 = Chk_Cfg according to EN 50170 (default state)
1 = User-specific evaluation of Chk_Cfg
Reserved. To be parameterised with '0'.
Enable_Update_Alarm
0 = Enable_Update_Alarm disabled
1 = Enable_Update_Alarm enabled (Not supported)
Enable_Status_Alarm
0 = Enable_Status_Alarm disabled
1 = Enable_Status_Alarm enabled (Not supported)
Enable_Manufacturer_Specific_Alarm
0 = Enable_Manufacturer_Specific_Alarm disabled
1 = Enable_Manufacturer_Specific_Alarm enabled
(Not supported)
Enable_Diagnostic_Alarm
0 = Enable_Diagnostic_Alarm disabled
1 = Enable_Diagnostic_Alarm enabled (Not
supported)
Enable_Process_Alarm
0 = Enable_Process_Alarm disabled
1 = Enable_Process_Alarm enabled (Not supported)
Enable_Pull_Plug_Alarm
0 = Enable_Pull_Plug_Alarm disabled
1 = Enable_Pull_Plug_Alarm enabled (Not
supported)
LSB
Alarm_Mode. Limits the number of active alarms.
0 = 1 alarm of each type
2 = 4 alarms in total
4 = 12 alarms in total
6 = 24 alarms in total
Prm_Structure
0 = Prm telegram according to EN 50170
1 = Prm telegram in structure form (DPV2 extension)
(Not supported)
IsoM_Req (Isochron Mode Request)
0 = Isochron Mode disabled
1 = Isochron Mode enabled (Not supported)
Reserved. To be parameterised with '0'.
1 = 2 alarms in total
3 = 8 alarms in total
5 = 16 alarms in total
7 = 32 alarms in total