7.1 General

The Searchline Excel Cross-Duct Transmitter and Receiver unit is certified to Ex d and has the following ATEX,
IECEx and UL approvals for worldwide acceptance:
ATEX, IECEx
II 2 G Ex d IIC T5 (Tamb -40 to +65°C) Gb
Ex d IIC T6 (Tamb -40 to +40°C)
Certificate numbers:
BAS98ATEX2165X
IECEx BAS 09.0100X
UL
Class 1 Groups B, C, D
Class 1 Zone 1 AEx d IIB + Hydrogen (Amb -40°C to +65°C)
File No. E91044
The Searchline Excel Cross-Duct Heated Reflector Panel is certified to Ex d and has the following ATEX and
UL approvals for worldwide acceptance:
ATEX
II 2 G Ex d IIC Gb T3 (Tamb -40 to +60°C)
Certificate number:
Baseefa06ATEX0226X
UL
Class 1, DIV 1, Groups B, C, D
Tamb -40 to +60°C
File No. E91044
The Searchline Excel system has been designed, built and tested to meet the latest European standards for
Radio Frequency Immunity (RFI). It has been tested and approved to BS EN 50270.