Installation Guide and Operating Manual Multi-Spectrum Digital Electro-Optical Fire Detectors Models SS2-A, SS2-AN, SS2-AH, and SS2-AM Stand-Alone Mode...
Page 2
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Page 3
OPERATO OR MANUAL // S SYMBOL DEFINI ITIONS Symbo ol Definit t ions The followi ing table lists s those symb bols used in t his documen nt to denote certain con nditions. Symbol Definitio ATTENT TION: Identif fies informat tion that requ uires special c...
OPERATOR MA ANUAL // APPRO OVALS APPRO OVALS The Model l SS2 Optica al Fire Detec tors have be een manufac tured in compliance e with the re equirements of the ISO-9 9001 standar rd and have been approved b ...
Model SS2-AN Detectors have a non-latching relay. They are otherwise identical to the SS2-A. Model SS2-AH is the same as Model SS2-A except for the programming to assure High Speed millisecond response to non-UV emitting sodium azide fires (in addition to the normal fire response) for air bag industries. The Detector is housed in a Class I, Div.
FS2000 System Controller using the four wire FS2000 FireBus. The FireBus provides the 24 Volts DC power for the Detector and RS-485 digital communication (Refer to Honeywell Analytics document MN0003: "FS2000 FIRE EARLY WARNING SYSTEM - INSTALLATION and OPERATIONS GUIDE").
Manual Testing For manual testing the Detector may be exposed to an actual industry standard open flame or to a Test Lamp simulating a fire. For Honeywell Analytics model SS2 Multi-Spectrum Fire Detectors, it is mandatory to use the handheld UV/IR Test Lamp, Model No FT-2045 or FT-2145.
Page 9
The FT-2045 and FT-2145 Test Lamps are housed in an Explosion-proof enclosure, powered by internal rechargeable batteries, and designed for indoor and outdoor use. For additional information on the Test Lamp, refer to Honeywell Analytics Specification SP0242 for the FT-2045 or 1505-008A for the FT-2145. HONEYWELL...
Detector's terminals and an Approved Fire Alarm Panel. Use only approved junction boxes and terminal strips. Avoid wire splices. However, if wire splices are necessary, Honeywell Analytics recommends soldering all splices. The use of good wiring practices will greatly improve the ease and reliability of installation, and facilitate servicing.
SM2 swivel-mount. Position the enclosure in such a way that the conduit openings are located horizontally at the bottom. Point the enclosure in the desired direction and tighten the appropriate hardware. 2.2.2 Install Conduit (If not already installed). Figure 2. Model SS2 Detector with SM2 Swivel Mount HONEYWELL...
OPERATOR MA ANUAL // SECTI ON 2: INSTALL LATION Wiring D Detectors To wire a M Model SS2 D Detector, rem move its mod dule from the e enclosure. After wiring con nections re-i install the m odule in the enclosure.
Page 13
OPERATOR MANUAL // SECTION 2: INSTALLATION Figure 4. Model SS2 Detector Enclosure - Back View HONEYWELL...
Page 15
Insert the Fault relay cables into the metal enclosure base through one of the conduit openings. b. Connect the wires to the four pin WECO terminal J2. Install the wires into J2 Pins 1 and 2 and firmly tighten down the slotted screws with a small screwdriver. HONEYWELL...
Page 16
If necessary, clean the detectors and windowed cover according to the instructions in Section 3.2. c. Screw down the metal enclosure top windowed cover until secure and tighten the allen-head "tamper-proof" screw. HONEYWELL...
OPERA ATOR MANUAL // SECTION 3 / MAINTENANC CE AND TROUBLESHO OTING SECTI ON 3 / M MAINTEN NANCE A AND TRO OUBLESH HOOTING Personn Troublesho ooting, testin ng, and main ntenance mu st be perform med only by qualified a authorized pe ersonnel obs serving stand...
2 DETECTO RFORMANCE ARNING: Po otential electr rostatic haza ard. Do not r ub with dry c cloth. SS2-A, - AN, -AH, a and –AM D Detectors’ ’ Faults Model SS2 Detectors wi ill indicate a F Fault (or Trou...
TROUBLESHO OTING SS2-A, - AN, -AH, a and -AM D Detector M Modules Re eplaceme AUTION: Mod del SS2-A, - AN, -AH, an d -AM Detec ctor modules s and eir componen nts are susce eptible to pe ermanent dam...
3 NOT USED (Do not connect anything to this Pin.) 4 Power (+24 Volts D.C.) J2: FAULT RELAY J2: FIRE RELAY #2 (SS2-A, -AN, -AM, -AML, AH) (SS2-AMD, -AMDL, -AHD) 1 Fault Relay Common 1 Fire Relay #2 Common 2 Fault Relay Normally Closed...
II 2 G Ex db IIC T6…T4 Gb II 2 Ex tb IIIC T135̊ C IP66 IEC 60067-0: 2011 IEC 60079-1: 2014 IEC 60079-31: 2013 IEC 60529: 2013 EN 60079-0: 2012 EN 60079-1: 2014 EN 60079-31: 2014 EN 60529 +A2: 2013 HONEYWELL...
Page 23
Honeywell Analytics warrants its Products against defects in material and workmanship under normal use and service for a period of two (2) years from the date of shipment as described herein. Honeywell Analytics, at its option, will repair or replace, at no charge, such products found to be defective during the warranty period provided that they are returned in accordance with the terms of this warranty.
Page 24
Honeywell Analytics Asia Pacific Co., Ltd. #701 Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Email: analytics.ap@honeywell.com Internet These Honeywell websites may be of interest to Industry Solution customers. Honeywell Organization Corporate www.honeywell.com Honeywell Analytics www.honeywellanalytics.com Telephone Contact us by telephone at these numbers.