Diagnose Menu - Honeywell Searchline Excel Cross-Duct Technical Handbook

Infrared gas detector
Hide thumbs Also See for Searchline Excel Cross-Duct:
Table of Contents

Advertisement

MAN0889_Issue 3_03/13
Appendix A - Handheld Interrogator
Normal mA
This menu option returns the system to its normal analogue output state, irrespective of its previous state. If
successful, the following message is displayed for three seconds:
Show Status
This menu option displays the calibration and configuration status of the system. The status information is
displayed in the following format:
where:
cccccccc... Title of the calibration status field.
sssssssss
The different settings from the list are selected using the ▲ and ▼ keys on the keypad.
The calibration status fields and values are given below:
Calibration Status Fields
Temperature Cal.
Zero Calibration
Span Calibration
4-20mA Calibration
Det. Temp. Comp.
Det. Sens. Comp.
Installation
Valid Date Time
Loop Test
A.5.4 Diagnose Menu
This sub menu has the following options:
Active Faults
Display the active faults in the system.
Active Warns
Display the active warnings in the system.
Self Test
Perform a diagnostic system self test.
Soft Reset
Reset the system.
Active Faults
This menu option displays operational faults when the system is in service.
4-20mA Released
ccccccccccccccc
Current state of calibration.
Display Text
Temp Sensor
Zero Ratio
Span Sensitivity
Analogue Output
T Compensation
Det Sensitivity
Installation
Date and Time
Analogue Check
Searchline Excel Cross-Duct Technical Handbook
False State
Uncalibrated
Uncalibrated
Uncalibrated
Uncalibrated
Uncalibrated
Uncalibrated
Required
Estimated
Failed
63
True State
Calibrated
Calibrated
Calibrated
Calibrated
Calibrated
Calibrated
Complete
Set
Passed