Conversion Characteristics of Analog Output

5.1 Voltage Range

5.1.1 Voltage Output Range: -10 to +10 V (0.32 mV, 1/62,500)

5-2
Output range: -10 to +10 V
Digital input
value
(K)
+31,250
+25,000
+18,750
+12,500
+6,250
0
-6,250
-12,500
-18,750
-25,000
-31,250
When exceeding the rated range
Digital input
value
+32,500 or more
-32,500 or less
Analog output
value
(V)
+10
+8
+6
+4
+2
0
-2
-4
-6
-8
-10
Analog output
value
Output at +10.4 V